Airtight Access Panels: Why They Matter and How They’re Measured

Airtightness is now a key consideration in modern construction, driven by energy efficiency requirements and tighter building regulations. While walls, floors, and glazing are often the focus, access panels can be a weak point if not properly specified.

Airtight access panels are designed to minimise uncontrolled air leakage, helping maintain building performance and compliance.

Why airtightness matters

Uncontrolled air leakage can lead to:

  • Heat loss, increasing energy consumption
  • Reduced thermal efficiency, affecting U-value performance
  • Condensation risk, potentially leading to long-term damage
  • Poor indoor comfort, with drafts and inconsistent temperatures

In the UK, airtightness is closely linked to Building Regulations Part L, which sets requirements for energy performance in buildings.

What is an airtight access panel?

An airtight access panel is designed to limit the amount of air passing through the panel and its frame when installed into a wall or ceiling.

This is achieved through:

  • Continuous perimeter seals or gaskets
  • Precision manufacturing tolerances
  • Secure locking mechanisms to maintain compression
  • Robust frame design to prevent distortion

The goal is to ensure the panel performs as part of the overall air barrier, rather than compromising it.

Anatomy of an airtight access panel: perimeter gasket, multi-point locking, frame tolerances and robust frame

How airtightness is tested

Airtight access panels are typically tested in accordance with BS EN 1026:2016 — Air Permeability Testing. This standard measures how much air passes through a product when subjected to pressure differences.

During testing:

  • Air pressure is applied to both sides of the panel (negative and positive pressures)
  • Leakage is measured at different pressure levels (e.g. 50 Pa)
  • Results are expressed as air permeability (m³/h/m²)

Lower values indicate better airtightness performance.

How airtightness is tested to BS EN 1026: positive and negative air pressure applied to an access panel in a test rig

Understanding air permeability results

Test results are often quoted at 50 Pascals (Pa), which is a common reference pressure. For example:

  • Lower m³/h/m² = better airtight performance
  • Results may differ slightly between positive and negative pressure tests

In some cases, products may also be classified into performance classes (e.g. Class 1–4), depending on the test method and application.

Where airtight panels are used

Airtight access panels are commonly specified in:

  • Residential developments (to meet Part L requirements)
  • Commercial buildings with strict energy targets
  • Schools and healthcare environments
  • Plant rooms and service risers within airtight envelopes

They are particularly important where the panel sits within the primary air barrier line of the building.

Airtightness vs fire & acoustic performance

Airtight performance is often required alongside other criteria, such as:

A well-designed access panel can combine these properties, but each must be individually tested and verified.

Installation matters

Even the highest-performing airtight panel can underperform if installed incorrectly.

Key considerations include:

  • Proper sealing between frame and structural opening
  • Use of appropriate sealants and fixings
  • Installation in line with tested details

Airtightness is only as strong as the weakest point in the system.

Key takeaway

Airtight access panels play a vital role in maintaining building performance by:

  • Reducing unwanted air leakage
  • Supporting compliance with Part L
  • Improving energy efficiency and comfort

When selecting access panels, ensure they are backed by verified air permeability test results, proven design and sealing systems, and clear installation guidance. This ensures the panel performs as part of the overall building envelope, not against it.

Related reading

Ready to specify?

Browse the Airtight Access Panels range, or for stacked airtight, fire and acoustic specifications contact the Technical Service team for verified test evidence and installation detail drawings.

FAQs

What is an airtight access panel?

An airtight access panel is designed to limit the amount of air passing through the panel and its frame when installed into a wall or ceiling. This is achieved through continuous perimeter seals or gaskets, precision manufacturing tolerances, secure locking mechanisms that maintain compression, and a robust frame design that resists distortion.

Why does airtightness matter?

Uncontrolled air leakage can cause heat loss and higher energy consumption, reduced thermal efficiency that affects U-value performance, condensation risk that can lead to long-term damage, and poor indoor comfort with drafts and inconsistent temperatures. In the UK, airtightness is closely linked to Building Regulations Part L.

How are airtight access panels tested?

Airtight access panels are typically tested in accordance with BS EN 1026:2016, the air permeability test standard. Air pressure is applied to both sides of the panel under negative and positive pressures, leakage is measured at different pressure levels such as 50 Pa, and results are expressed as air permeability in m³/h/m². Lower values indicate better performance.

What do air permeability results mean?

Results are often quoted at 50 Pascals, a common reference pressure. A lower m³/h/m² figure means better airtight performance, and results may differ slightly between positive and negative pressure tests. In some cases products are also classified into performance classes (e.g. Class 1–4), depending on the test method and application.

Where are airtight access panels used?

They are commonly specified in residential developments meeting Part L requirements, commercial buildings with strict energy targets, schools and healthcare environments, and plant rooms or service risers within airtight envelopes. They are particularly important where the panel sits within the primary air barrier line of the building.

Can airtight access panels also be fire or acoustic rated?

Yes. Airtight performance is often required alongside fire resistance and acoustic performance. A well-designed access panel can combine these properties, but each criterion must be individually tested and verified.

Does installation affect airtightness?

Yes. Even the highest-performing airtight panel can underperform if installed incorrectly. Key factors are proper sealing between the frame and structural opening, the use of appropriate sealants and fixings, and installation in line with tested details. Airtightness is only as strong as the weakest point in the system.

Fire Ratings Explained: Understanding E, EI and Fire Resistance Performance

Fire ratings are commonly referenced throughout construction projects, but the terminology can often cause confusion. Understanding what a fire rating actually means is essential when specifying access panels, riser doors, and other compartmentation products.

Fire ratings are used to describe how long a product can maintain its performance when exposed to fire under controlled test conditions.

What is a fire rating?

A fire rating is the classification given to a product after successful fire resistance testing. The rating confirms how long the product can withstand fire exposure while maintaining specific performance criteria.

Typical fire ratings include:

  • E30
  • EI30
  • EI60
  • EI120

The number refers to the duration, in minutes, that the product achieved during testing. For example:

  • 30 = 30 minutes
  • 60 = 60 minutes
  • 120 = 120 minutes

What a fire rating means: E30, EI30, EI60 and EI120 and the duration each represents

ClassificationIntegrityInsulationDuration
E30Yes30 minutes
EI30YesYes30 minutes
EI60YesYes60 minutes
EI120YesYes120 minutes

What does “E” mean?

Integrity (E) measures the ability of a product to:

  • Prevent flames passing through
  • Restrict hot gases
  • Maintain compartmentation during a fire

A product classified as E30 has maintained integrity for 30 minutes during testing. This means the assembly prevented fire penetration for the tested duration, but it does not necessarily control heat transfer.

What does “EI” mean?

An EI classification includes both:

  • Integrity (E), and
  • Insulation (I)

In addition to stopping flames and hot gases, insulation limits the temperature rise on the non-fire side of the product. This helps reduce:

  • Heat transfer
  • Ignition risk to nearby materials
  • Radiated heat into adjacent areas

For example, EI60 means 60 minutes of integrity and insulation performance.

E versus EI fire ratings: E (integrity) stops flames and hot gases, EI also limits heat transfer

PerformanceE — IntegrityEI — Integrity & Insulation
Stops flames and hot gasesYesYes
Limits heat transfer to the protected sideYes

Why insulation matters

An integrity-only product may stop flames but still allow significant heat transfer through the surface. An insulated product helps maintain safer temperatures on the protected side of the wall or ceiling construction.

This can be particularly important in:

  • Escape routes
  • Protected corridors
  • Residential compartment walls
  • High-risk environments

How fire ratings are achieved

Fire ratings are determined through laboratory testing, commonly to BS EN 1634-1:2014 + A1:2018.

During testing:

  • The product is installed into a representative wall or ceiling construction
  • It is exposed to controlled furnace temperatures
  • Performance is monitored over time

The test continues until failure criteria are reached.

Furnace temperatures rise rapidly

Fire tests follow a standard time–temperature curve, where temperatures increase rapidly. Typical furnace temperatures can exceed:

  • 500°C within minutes
  • 800°C+ during longer-duration tests

This places significant stress on door leaves, frames, seals, locking systems and ironmongery.

Fire ratings and real-world applications

Different buildings and applications require different levels of fire performance. Examples may include:

  • Service risers
  • Corridors
  • Plant rooms
  • Ceiling void access
  • Protected escape routes

The required fire rating will normally be determined by the building design, compartmentation strategy, Building Regulations and fire engineer requirements.

Fire rated does not mean everything is covered

A fire rating only applies to:

  • The tested construction
  • The tested configuration
  • The tested installation method

Changes to wall type, hardware, frame design, panel size or installation method may affect performance unless covered by further assessment or extended application evidence.

Installation is just as important

Even a successfully fire-tested product can underperform if installed incorrectly. Correct installation is critical to maintaining:

  • Seal compression
  • Structural support
  • Compartmentation integrity

Always follow manufacturer installation guidance, tested construction details, and approved fixing and sealing methods.

Key takeaway

Fire ratings provide a recognised way of understanding how a product performs during fire exposure.

  • E = Integrity only
  • EI = Integrity and insulation

The number indicates how many minutes the product achieved under test conditions.

Final thoughts

When specifying fire-rated access panels or riser doors, it’s important to look beyond the headline rating alone. Always consider the wall or ceiling construction, the installation method, supporting test evidence, and whether integrity-only or insulation is required.

A correctly tested and installed product plays a vital role in maintaining compartmentation and supporting building safety.

Related reading

Ready to specify?

Browse the fire-rated access panel and riser door ranges, or contact the Technical Service team for BS EN 1634-1 test evidence and installation detail drawings.

FAQs

What is a fire rating?

A fire rating is the classification given to a product after successful fire resistance testing. The rating confirms how long the product can withstand fire exposure while maintaining specific performance criteria. Typical fire ratings include E30, EI30, EI60 and EI120 — the number refers to the duration, in minutes, that the product achieved during testing.

What does the "E" in a fire rating mean?

E stands for integrity. Integrity measures a product’s ability to prevent flames passing through, restrict hot gases, and maintain compartmentation during a fire. A product classified as E30 maintained integrity for 30 minutes during testing — it prevented fire penetration for the tested duration, but does not necessarily control heat transfer.

What does the "EI" in a fire rating mean?

EI means integrity and insulation. In addition to stopping flames and hot gases, insulation limits the temperature rise on the non-fire side of the product. This helps reduce heat transfer, ignition risk to nearby materials, and radiated heat into adjacent areas. For example, EI60 means 60 minutes of integrity and insulation performance.

Why does insulation matter?

An integrity-only product may stop flames but still allow significant heat transfer through its surface. An insulated product helps maintain safer temperatures on the protected side of the wall or ceiling. This is particularly important in escape routes, protected corridors, residential compartment walls and high-risk environments.

How are fire ratings achieved?

Fire ratings are determined through laboratory testing, commonly to BS EN 1634-1:2014 + A1:2018. The product is installed into a representative wall or ceiling construction, exposed to controlled furnace temperatures following a standard time-temperature curve, and monitored over time until failure criteria are reached. Furnace temperatures can exceed 500°C within minutes and 800°C during longer tests.

Does a fire rating cover every situation?

No. A fire rating only applies to the tested construction, the tested configuration and the tested installation method. Changes to wall type, hardware, frame design, panel size or installation method may affect performance unless covered by further assessment or extended application evidence.

Does installation affect fire performance?

Yes. Even a successfully fire-tested product can underperform if installed incorrectly. Correct installation is critical to maintaining seal compression, structural support and compartmentation integrity. Always follow manufacturer installation guidance, tested construction details, and approved fixing and sealing methods.